Extension of institutional technical standards: bolted steel tank with vitreous enamel coating and PVC pipes for wastewaterAmpliación de normas técnicas institucionales: tanque pernado de acero revestido con vidrio termofusionado y tuberías de PVC para agua residual

View document ↓ Ver documento ↓ View original source ↗ Ver fuente original ↗

Loading…Cargando…

OutcomeResultado

Active lawNorma vigente

Modifications to two AyA institutional technical specifications are approved, regarding materials and design for steel tanks and PVC pipes for sanitation systems.Se aprueban modificaciones a dos especificaciones técnicas institucionales del AyA sobre materiales y diseño de tanques de acero y tuberías de PVC para sistemas de saneamiento.

SummaryResumen

This document from the Costa Rican Institute of Aqueducts and Sewers (AyA) approves partial amendments to two internal technical specifications. First, it adjusts specification AyA-1000-TQ-01 on bolted steel tanks with vitreous enamel coating, detailing requirements for tank foundations, sealing procedures using chlorine-compatible polyurethane to ensure watertightness, and making minor terminological corrections. Second, it modifies specification AyA-4000-TPVC-01-A01 on PVC pipes for underground conveyance of wastewater, either by gravity or under pressure. It defines acceptable diameters and materials for tertiary, secondary, and primary sewer networks, as well as for force mains, establishes exceptional minimum slopes, and updates references to ASTM and INTE standards. The aim is to ensure the technical quality of materials used in these sanitation systems.Este documento del Instituto Costarricense de Acueductos y Alcantarillados (AyA) aprueba modificaciones parciales a dos especificaciones técnicas internas. En primer lugar, se ajusta la especificación AyA-1000-TQ-01 sobre tanques de acero pernado con revestimiento de vidrio termofusionado, detallando requisitos para la fundación del tanque, los procedimientos de sellado para garantizar estanqueidad usando poliuretano compatible con cloro, y efectuando correcciones terminológicas menores. En segundo lugar, se modifica la especificación AyA-4000-TPVC-01-A01 sobre tuberías de PVC para conducción subterránea de aguas residuales, ya sea a gravedad o a presión. Se definen los diámetros y materiales aceptables para redes de alcantarillado terciarias, secundarias y primarias, así como para líneas de impulsión, estableciendo pendientes mínimas excepcionales y actualizando las referencias a normas ASTM e INTE. El objetivo es garantizar la calidad técnica de los materiales usados en estos sistemas de saneamiento.

Key excerptExtracto clave

The type of tank foundation must comply with the requirements established in ANSI/AWWA D103, with only types 1, 2, or 6 of said standard being acceptable. The selection of the tank foundation type must be supported by a technical analysis generated by the design professional and endorsed with their signature; this analysis must include a review of the overturning ratio. When selecting foundation type 6, the tank designer must demonstrate that the overturning ratio (J) does not exceed 0.785 and the design for type 6 must comply with the requirements set forth in section 4.5.1. For type 1 or type 2 foundations, the tank floor must be made of preformed steel sheets enameled with silica (glass) as provided in section 4.4, in addition to complying with the design and material requirements indicated in AWWA D103.El tipo de fundación del tanque debe cumplir con los requisitos establecidos en la norma ANSI/AWWA D103, siendo aceptables únicamente los tipos 1, 2 o 6 de dicha norma. La selección del tipo de fundación del tanque debe sustentarse en un análisis técnico generado por el profesional responsable del diseño y avalado con su firma; dicho análisis debe incluir la revisión de la razón de volcamiento. Cuando se selecciona la fundación tipo 6, el diseñador del tanque debe demostrar que la razón de volcamiento (J) no supera el valor de 0,785 y el diseño para el tipo 6 debe cumplir con los requisitos establecidos en el apartado 4.5.1. En el caso de las fundaciones tipo 1 o tipo 2, el piso del tanque debe ser de láminas de acero preformadas y esmaltadas con sílice (vidrio) según lo dispuesto en el apartado 4.4, además se debe cumplir con los requisitos de diseño y materiales indicados en la norma AWWA D103.

Pull quotesCitas destacadas

  • "El sellante debe ser de poliuretano de un solo componente y debe presentar una resistencia mínima al cloro de 10 ppm para una exposición continua durante 24 horas; además el sellante y sus aditivos deben cumplir con la norma ANSI/NSF 61."

    "The sealant must be a one-component polyurethane and must exhibit a minimum chlorine resistance of 10 ppm for continuous exposure for 24 hours; in addition, the sealant and its additives must comply with ANSI/NSF 61."

    Apartado 5.5

  • "El sellante debe ser de poliuretano de un solo componente y debe presentar una resistencia mínima al cloro de 10 ppm para una exposición continua durante 24 horas; además el sellante y sus aditivos deben cumplir con la norma ANSI/NSF 61."

    Apartado 5.5

  • "De forma excepcional, cuando la zona donde se instalará la tubería sea de topografía regular o presente restricciones de profundidad por aspectos operativos, previo razonamiento técnico que demuestre la imposibilidad de utilizar una pendiente igual o superior al 1%, debidamente documentado, el valor mínimo de la pendiente será de 0,60%."

    "Exceptionally, when the area where the pipe will be installed has regular topography or presents depth restrictions due to operational aspects, upon prior technical reasoning demonstrating the impossibility of using a slope equal to or greater than 1%, duly documented, the minimum slope value shall be 0.60%."

    Apartado 4.2.1

  • "De forma excepcional, cuando la zona donde se instalará la tubería sea de topografía regular o presente restricciones de profundidad por aspectos operativos, previo razonamiento técnico que demuestre la imposibilidad de utilizar una pendiente igual o superior al 1%, debidamente documentado, el valor mínimo de la pendiente será de 0,60%."

    Apartado 4.2.1

Full documentDocumento completo

throughout the entire text - Full Text of Standard 0 Amendment Expansion of institutional technical standards for bolted steel tanks lined with thermofused glass and Technical Specification AyA-4000-TPVC-01-A01 PVC Pipes for underground use in the conveyance of wastewater by gravity or under pressure COSTA RICAN INSTITUTE OF AQUEDUCTS AND SEWERS (AyA) Partial modification 1.1. Technical Specification AyA-1000-TQ-01 "Bolted steel tank lined with thermofused glass" (Agreement 2020-302).

1.1.1. The text "(tank wall" is removed from the title, and in section 4.4, the expression "The tank wall" is replaced with "The tank sheets." 1.1.2. Regarding the outlet pipe, the expression "(if located on the tank wall)" is removed from the third paragraph of section 4.4.2.

1.1.3. The content of section "4.5 Foundation" is modified to read as follows: "The type of tank foundation must comply with the requirements established in the ANSI/AWWA D103 standard, with only types 1, 2, or 6 of said standard being acceptable.

The selection of the tank foundation type must be supported by a technical analysis generated by the professional responsible for the design and endorsed with their signature; this analysis must include a review of the overturning ratio.

When a type 6 foundation is selected, the tank designer must demonstrate that the overturning ratio (J) does not exceed the value of 0.785, and the design for type 6 must comply with the requirements established in section 4.5.1.

In the case of type 1 or type 2 foundations, the tank floor must be made of preformed steel sheets enameled with silica (glass) as provided in section 4.4; in addition, the design and material requirements indicated in the AWWA D103 standard must be met." 1.1.4. The following three paragraphs are added to the beginning of section "5.5 Tank Leaktightness":

"In all internal and external areas of the tank where joints, bolts, and sheet edges exist, a sealant suitable for internal and external surfaces, as applicable, must be applied to prevent leaks.

The sealant must be a single-component polyurethane and must have a minimum chlorine resistance of 10 ppm for continuous exposure for 24 hours; furthermore, the sealant and its additives must comply with the ANSI/NSF 61 standard, for which the bidder must provide the corresponding certification together with the product's technical data sheet.

The use of neoprene gaskets and sealing tapes is only permitted on access doors or hatches for tank inspection." 1.1.5. The expression "(tank wall and roof)" is removed from section "5.8 Handling, storage, and transport." 1.1.6. The expression "that make up the wall" is removed from Annex 1.

1.1.7. Figure 1 is replaced with the following, in which the expression "Tank Wall" is replaced with "Tank Sheet." 1.2 Technical Specification AyA-4000-TPVC-01-A01. PVC pipe for underground use in the conveyance of wastewater by gravity or under pressure. Part 1: requirements for circular cross-section PVC pipe (Agreement 2021-266) 1.2.1 The content of section "4.2.1 Diameter" is modified to read as follows:

Pipe for gravity flow The use of pipe according to the ASTM D3034 standard is accepted for gravity flows, in tertiary networks (general sewer), secondary networks (subcollectors), primary networks (collectors), or planned networks, for the diameters defined in the Technical Standard for the Design and Construction of Potable Water Supply, Sanitation, and Stormwater Systems, with the provisions, caveats, or exceptions established in said technical standard issued by AyA, including matters related to its applications in wastewater sanitation systems.

Also, the use of pipe according to the ASTM F679 manufacturing standard is accepted for gravity flows, in secondary networks (subcollectors) or primary networks (collectors) starting from 450 mm in diameter, as is the use of pipe according to the ASTM F949 manufacturing standard for gravity flow, in tertiary networks (general sewer), secondary networks (subcollectors), or primary networks (collectors).

Pipe in gravity flows must be installed with a slope (pendiente) equal to or greater than 1% and must meet the minimum tractive force (fuerza tractiva) indicated in the Technical Standard for the Design and Construction of Potable Water Supply, Sanitation, and Stormwater Systems, issued by AyA.

Exceptionally, when the area where the pipe will be installed has regular topography or presents depth restrictions due to operational aspects, following a duly documented technical reasoning demonstrating the impossibility of using a slope (pendiente) equal to or greater than 1%, the minimum slope (pendiente) value shall be 0.60%; the foregoing, provided that the tractive force (fuerza tractiva) indicated in the Technical Standard for the Design and Construction of Potable Water Supply, Sanitation, and Stormwater Systems, issued by AyA, is met.

When the slope (pendiente) has a value equal to or greater than 0.60% and less than 1%, the technical-constructive details and technical specifications that guarantee compliance with these values in situ must be added.

All of the above is applied jointly with the provisions, caveats, or exceptions established in the corresponding parts of the Technical Standard for the Design and Construction of Potable Water Supply, Sanitation, and Stormwater Systems.

Pipe for pressure flow and siphons In the particular case of force mains and siphons, the use of pipe according to the INTE C173 (INTE 16-01-01) manufacturing standard is accepted, for the diameters defined in the Technical Standard for the Design and Construction of Potable Water Supply, Sanitation, and Stormwater Systems, with the provisions, caveats, or exceptions established in said technical standard issued by AyA.

The use of the INTE C175 (INTE 16-01-04) standard is also accepted; in this case, only schedule 40 and 80 pipe with a nominal diameter of 200 mm or less and for non-threaded pipe is permitted.

Consistent with the foregoing, and having verified the working pressure to which the pipe will be subjected, if the designer determines that the use of pipe for an SDR 26 (HDS 2000 psi) is required, the use of schedule 40 pipe is accepted as a substitute for this condition, maintaining the condition of a nominal diameter of 200 mm or less. Likewise, for the case of SDR 17 (HDS 2000 psi), the use of schedule 80 pipe is accepted as a substitute, maintaining the condition of a nominal diameter of 200 mm or less." 1.2.2 The versions of the following normative references, contained in section "6. Normative reference documents," are updated:

ASTM D2241: 2020 "Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)" ASTM D3034: 2021 "Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings" INTE C173: 2021 "Plastics - Poly(vinyl chloride) (PVC) pipes classified by working pressure (SDR Series)" INTE C175: 2021 "Poly(Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120" INTE C224: 2021 Structured-wall PVC pipes with smooth interior for sewerage and their fittings INTE Q73: 2022 "Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds - Requirements"

en la totalidad del texto - Texto Completo Norma 0 Reforma Ampliación de normas técnicas institucionales tanque pernado de acero revestido con vidrio termofusionado y Especificación Técnica AyA-4000-TPVC-01-A01 Tuberías de PVC de uso subterráneo para el trasiego de agua residual a gravedad o a presión INSTITUTO COSTARRICENSE DE ACUEDUCTOS Y DE ALCANTARILLADOS (AyA) AMPLIACIÓN DEL VOLUMEN IV "ESPECIFICACIONES TÉCNICAS GENERALES DE AYA" Modificación parcial 1.1. Especificación Técnica AyA-1000-TQ-01 "Tanque de acero pernado revestido con vidrio termofusionado" (Acuerdo 2020-302).

1.1.1. Se elimina del título el texto "(pared del tanque" y se sustituye en el apartado 4.4 la expresión "La pared del tanque" por "Las láminas del tanque".

1.1.2. Respecto a la tubería de salida, se elimina del párrafo tercero del apartado 4.4.2 la expresión "(en caso de ubicarse en la pared del tanque).

1.1.3. Se modifica el contenido del apartado "4.5 Fundación" para que se lea de la siguiente forma: "El tipo de fundación del tanque debe cumplir con los requisitos establecidos en la norma ANSI/AWWA D103, siendo aceptables únicamente los tipos 1, 2 o 6 de dicha norma.

La selección del tipo de fundación del tanque debe sustentarse en un análisis técnico generado por el profesional responsable del diseño y avalado con su firma; dicho análisis debe incluir la revisión de la razón de volcamiento.

Cuando se selecciona la fundación tipo 6, el diseñador del tanque debe demostrar que la razón de volcamiento (J) no supera el valor de 0,785 y el diseño para el tipo 6 debe cumplir con los requisitos establecidos en el apartado 4.5.1.

En el caso de las fundaciones tipo 1 o tipo 2, el piso del tanque debe ser de láminas de acero preformadas y esmaltadas con sílice (vidrio) según lo dispuesto en el apartado 4.4, además se debe cumplir con los requisitos de diseño y materiales indicados en la norma AWWA D103." 1.1.4. Se adiciona al inicio del apartado "5.5 Estanqueidad del tanque" los siguientes tres párrafos:

"En todas las áreas internas y externas del tanque en las que exista uniones, pernos y bordes de láminas se debe aplicar un sellador apto para superficies internas y externas según corresponda, para evitar filtraciones El sellante debe ser de poliuretano de un solo componente y debe presentar una resistencia mínima al cloro de 10 ppm para una exposición continua durante 24 horas; además el sellante y sus aditivos deben cumplir con la norma ANSI/NSF 61, para ello el oferente debe aportar la certificación correspondiente en conjunto con la ficha técnica del producto.

Únicamente se admite el uso de empaques de neopreno y cintas selladoras en las puertas o compuertas de acceso para inspección del tanque." 1.1.5. Se elimina del apartado "5.8 Manipulación, almacenamiento y transporte" la expresión "(pared del tanque y del techo)".

1.1.6. Se elimina del anexo 1 la expresión "que conforman la pared".

1.1.7. Se sustituye la figura 1 por la siguiente, en la cual se sustituye la expresión "Pared de tanque" por "Lámina de tanque".

1.2 Especificación Técnica AyA-4000-TPVC-01-A01. Tubería de PVC de uso subterráneo para el trasiego de agua residual a gravedad o a presión. Parte 1: requisitos de la tubería de PVC de sección circular (Acuerdo 2021-266) 1.2.1 Se modifica el contenido del apartado "4.2.1 Diámetro" para que se lea de la siguiente forma:

Tubería para flujo a gravedad Se acepta el uso de tubería según la norma ASTM D3034 en flujos a gravedad, en redes terciarias (red general), redes secundarias (subcolectores), redes primarias (colectores) o previstas, para los diámetros definidos en la Norma Técnica de Diseño y Construcción de Sistemas de Abastecimiento de Agua Potable, de Saneamiento y Pluvial, con las disposiciones, salvedades o excepciones establecidas en dicha norma técnica emitida por AyA, incluido lo relacionado con sus aplicaciones en sistemas de saneamiento de aguas residuales.

También, se acepta el uso de la tubería según la norma de fabricación ASTM F679 en flujos por gravedad, en redes secundarias (subcolectores) o redes primarias (colectores) a partir de 450 mm de diámetro, así como el uso de la tubería según la norma de fabricación ASTM F949 en flujo por gravedad, en redes terciarias (red general), redes secundarias (subcolectores) o redes primarias (colectores).

La tubería en flujos a gravedad debe instalarse con una pendiente igual o superior al 1% y debe cumplir la fuerza tractiva mínima indicada en la Norma Técnica de Diseño y Construcción de Sistemas de Abastecimiento de Agua Potable, de Saneamiento y Pluvial, emitida por AyA.

De forma excepcional, cuando la zona donde se instalará la tubería sea de topografía regular o presente restricciones de profundidad por aspectos operativos, previo razonamiento técnico que demuestre la imposibilidad de utilizar una pendiente igual o superior al 1%, debidamente documentado, el valor mínimo de la pendiente será de 0,60%; lo anterior, siempre que se cumpla con la fuerza tractiva indicada en la Norma Técnica de Diseño y Construcción de Sistemas de Abastecimiento de Agua Potable, de Saneamiento y Pluvial, emitida por AyA.

Cuando la pendiente tenga un valor igual o superior a 0,60% y menor al 1%, se deben adicionar los detalles técnico-constructivos y especificaciones técnicas que garanticen el cumplimiento de estos valores in situ.

Todo lo anterior, se aplica conjuntamente con las disposiciones, salvedades o excepciones establecidas en la Norma Técnica de Diseño y Construcción de Sistemas de Abastecimiento de Agua Potable, de Saneamiento y Pluvial, en lo correspondiente.

Tubería para flujo a presión y sifones En el caso particular de líneas de impulsión y sifones, se acepta el uso de tubería según la norma de fabricación INTE C173 (INTE 16-01-01), para los diámetros definidos en la Norma Técnica de Diseño y Construcción de Sistemas de Abastecimiento de Agua Potable, de Saneamiento y Pluvial, con disposiciones, salvedades o excepciones establecidas en dicha norma técnica emitida por AyA.

También se acepta el uso de la norma INTE C175 (INTE 16-01-04), para este caso únicamente se admite tubería de cédula 40 y 80 en un diámetro nominal de 200 mm o inferior y para tubería no roscada.

Consecuente con lo anterior y verificada la presión de trabajo a la que estará sometida la tubería, si el diseñador determina que se requiere el uso de tubería para un SDR 26 (HDS 2000 psi), para esta condición se acepta como sustituto el uso de tubería cédula 40, manteniendo la condición del diámetro nominal de 200 mm o inferior. Así mismo, para el caso del SDR 17 (HDS 2000 psi), se acepta como sustituto el uso de tubería cédula 80, manteniendo la condición del diámetro nominal de 200 mm o inferior." 1.2.2 Se actualizan las versiones de las siguientes referencias normativas, contenidas en el apartado "6. Documentos normativos de referencia":

ASTM D2241: 2020 "Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)" ASTM D3034: 2021 "Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings" INTE C173: 2021 "Plásticos - Tubos de poli(cloruro de vinilo) (PVC) clasificados según la presión de trabajo (Serie SDR)" INTE C175: 2021 "Tubería plástica de Poli (Cloruro de vinilo) (PVC) cédula 40,80 y 120" INTE C224: 2021 Tuberías de PVC de pared estructurada con interior liso para alcantarillado y sus accesorios INTE Q73: 2022 "Compuestos de Poli (Cloruro de Vinilo) (PVC) Rígido y Compuestos de Poli (Cloruro de Vinilo) Clorado (CPVC) - Requisitos"

Document not found. Documento no encontrado.

Implementing decreesDecretos que afectan

    TopicsTemas

    • Off-topic (non-environmental)Fuera de tema (no ambiental)

    Concept anchorsAnclajes conceptuales

      Spanish key termsTérminos clave en español

      Article 1

      Artículo 1

      News & Updates Noticias y Actualizaciones

      All articles → Todos los artículos →

      Weekly Dispatch Boletín Semanal

      Field reporting and policy analysis from Costa Rica's forests. Reportajes y análisis de política desde los bosques de Costa Rica.

      ✓ Subscribed. ✓ Suscrito.

      One email per week. No spam. Unsubscribe in one click. Un correo por semana. Sin spam. Cancela en un clic.

      Or WhatsApp channelO canal de WhatsApp →
      Coalición Floresta © 2026 · All rights reserved © 2026 · Todos los derechos reservados

      Stay Informed Mantente Informado

      Conservation news and action alerts, straight from the field Noticias de conservación y alertas de acción, directo desde el campo

      Email Updates Actualizaciones por Correo

      Weekly updates, no spam Actualizaciones semanales, sin spam

      Successfully subscribed! ¡Suscripción exitosa!

      WhatsApp Channel Canal de WhatsApp

      Join to get instant updates on your phone Únete para recibir actualizaciones instantáneas en tu teléfono

      Join Channel Unirse al Canal
      Coalición Floresta Coalición Floresta © 2026 Coalición Floresta. All rights reserved. © 2026 Coalición Floresta. Todos los derechos reservados.
      🙏